Bronkhorst

MAG-VIEW MVM-002-PA

Low-Flow Magnetic Inductive Flow meters for water-like liquids

  • Compact, weatherproof (IP65) design
  • No moving parts (no mechanical wear)
  • Interference free operation
  • Independence to inlet/outlet pipework
  • Fast response
  • Free pipe cross section: low ΔP, insensitive to contamination
  • Analog output (4...20 mA)
MASSFLOW-ONLINE product
  お見積り依頼 Downloads Buy now Datasheet
MAG-VIEWMVM-002-PA

Electromagnetic flow meters for low flow rates of water and aqueous solutions

MAG-VIEW instruments are electromagnetic inductive flow meters for electrically conductive liquids with a minimum conductivity of 50 μS/cm. The compact, weatherproof (IP65) flow meters do not contain any moving parts, cause virtually no pressure loss and can be mounted in any position, requiring no straight inlet or outlet runs.

MAG-VIEW flow meter model MVM-002-PA has a nominal diameter of DN2 for flow rates of 0,05...2 l/min, suited for operating pressures up to 16 bar(g). The instrument allows frequency and analog output (4...20 mA) proportional to the flow.


Technical specifications

Measurement / control system
流量レンジ0,05 … 2 l/min
Volume flow accuracy±1% RD at 0...50% of measuring range
±2% RD at 50...100% of measuring range
(incl. factory calibration certificate; test conditions: water 23°C)
Turndown ratio1:40
Reproducibility1 % FS
Signal output starting from~ 0,05 l/min
MediaWater and other conductive liquids
(minimum conductivity of 50 μS/cm)
Response time (sensor)< 500 msec
Medium temperature-20 … 90 °C
MountingAny position, attitude insensitive
Flow indicationgreen LED, flow proportional flashing
Mechanical parts
Material (wetted parts)Electrodes: Stainless Steel 1.4571
Process connections: Stainless Steel 1.4571
Measuring pipe: PEEK-GF30
Gasket: EPDM
HousingAluminium pressure diecasted
DiameterDN2
Process connections1/4" BSP male thread
Ingress protectionIP65
Nominal pressurePN16
Electrical properties
Power supply24 Vdc ±10 %
Max. power consumption150 mA
Analog output4…20 mA, max. load 250 Ω to GND
Frequency outputPulse rate / K-factor : 10000 pulses/l
Resolution : 0,1 ml/pulse
Signal shape : Square wave signal - duty cycle 50:50
Push-Pull - NPN open collector [o.c.] - PNP o.c.
Signal current : max. 100 mA, current limited
Electrical protection measuresShort-circuit proof, protected against polarity reversal
Electrical connection5-pin-plug M12x1
Electrical connection
Control valve options
External actuator options to be connected to the controller
Certification for hazardous areas
Approvals / certificates

Technical specifications subject to change without notice.

For dimensional drawings and hook-up diagrams please visit the product page on our website

Downloads

Brochures
MAG-VIEW Brochure


ブロンコスト・ジャパン株式会社
〒135-0016
東京都江東区東陽5-27-5

Tel.  03-3645-1371

sales◎bronkhorst.jp   ◎を@に置き換えて下さい

     
Copyright © 2024 Bronkhorst. All rights reserved.     サイトマップ     免責事項     プライバシーポリシー